Common AC Cooling Diagnosis Reference
Why this matters
"AC isn't cooling" is the most common HVAC complaint in cooling season. Multiple possible causes; correct diagnosis matters for first-time fix. The tech who systematically diagnoses cooling complaints earns trust + saves time. This is the field card.
AC system basics
Components:
- Compressor (outdoor): pumps refrigerant
- Condenser coil (outdoor): releases heat to outside
- Condenser fan: moves air across condenser
- Expansion device (TXV / piston / orifice): meters refrigerant
- Evaporator coil (indoor): absorbs heat from inside
- Blower (indoor): moves air across evaporator
- Refrigerant: transfers heat between coils
Process:
- Liquid refrigerant evaporates in evaporator (absorbs heat from inside)
- Vapor compressed by compressor
- Vapor condenses in condenser (releases heat outside)
- Liquid returns to evaporator
- Cycle repeats
Common customer complaints
"AC not cooling at all":
- Compressor not running
- Power issue
- Capacitor failed
- Refrigerant lost completely
- Failure of major component
"AC running but not cool enough":
- Refrigerant low
- Dirty filter / coils
- Iced evaporator
- Compressor failing
- Undersized for conditions
"AC short-cycles":
- Thermostat issue
- Oversized for load
- Compressor overload
- Pressure issue
"AC freezes up":
- Low refrigerant
- Low airflow (dirty filter, blocked vents)
- Closed too many vents
- Thermostat set too low
"AC blows warm air":
- Outdoor unit not running
- Refrigerant low
- Indoor coil iced
- Compressor failed
"AC noisy":
- Fan blade damaged
- Bearing failing
- Compressor labored
- Refrigerant gurgling (low charge)
Diagnostic sequence
For "AC not cooling":
- Verify customer setpoint (thermostat set correctly?)
- Verify call for cool (thermostat showing cool calling?)
- Check filter (most common; clogged restricts airflow)
- Verify indoor unit running (blower? air at registers?)
- Verify outdoor unit running (compressor humming? fan spinning?)
- Check temperatures (return air vs supply air; 15-20°F delta normal)
- Check refrigerant (gauges + manufacturer charge chart)
- Identify root cause
Power diagnostics
No outdoor unit operation:
- Disconnect switch off (check at outdoor)
- Breaker tripped
- Contactor failed
- Capacitor failed
- 24V control signal missing (from thermostat / control)
Outdoor unit hums but won't start:
- Capacitor failed (most common)
- Compressor seized
- Locked rotor
- Hard-start kit needed (sometimes)
Indoor blower not running:
- Filter clogged (some systems shut down)
- Blower motor failed
- Capacitor (PSC motor) failed
- Limit switch tripped
- Float switch tripped (drain pan full)
Refrigerant diagnostics
Gauge readings:
Standard residential R-410A:
- Low side (suction): ~100-130 PSI (varies with outdoor temp)
- High side (discharge): ~250-400 PSI (varies with outdoor temp)
Low charge symptoms:
- Low side too low
- High side lower than expected
- Suction line cold OR icy
- Compressor short-cycling
- Insufficient cooling
High charge symptoms:
- Both pressures elevated
- Liquid back to compressor (slugging)
- Compressor failure risk
No charge:
- Both pressures low
- No cooling
- Often discoverable leak
Use manufacturer charge chart:
- Outdoor temp + indoor return temp = expected pressures
- Don't guess
Refrigerant leak detection
Electronic leak detector:
- Sniff fittings + components
- Most sensitive
Bubble solution:
- Soap solution on suspected fittings
- Bubbles = leak
- Simple + effective
UV dye:
- Added to refrigerant; black light reveals
- For hidden leaks
Common leak locations:
- Service valves
- Schrader cores
- Fitting connections
- Evaporator coil (most common in older systems)
- Condenser coil
- Compressor
Airflow diagnostics
Filter:
- Check first
- Replace if dirty
- Some systems have specific issues with high-MERV filters (too restrictive)
Ductwork:
- Verify supply registers open
- Check returns clear
- Check for collapsed flex duct
Blower:
- Wheel clean?
- Speed setting (multi-tap motor)
- Motor running correctly
- Capacitor (PSC) good?
External static pressure:
- Measure total static
- High SP = airflow restricted
- Low SP = duct leak
Evaporator icing
When evaporator ices over:
Symptoms:
- Reduced airflow
- Reduced cooling
- Eventually no airflow
- Sometimes blower water on floor
Causes:
- Low refrigerant (#1)
- Low airflow (filter, blower issue)
- Thermostat set too low (running constantly)
- Too many vents closed
Resolution:
- Shut off AC; let ice melt (turn fan on to speed)
- Don't restart until thawed
- Diagnose underlying cause
- Address before reoperating
Coil cleaning
Outdoor coil dirty:
- Reduces heat transfer
- Higher discharge pressure
- Less cooling
- Higher energy use
Cleaning:
- Hose from inside out (fins direction)
- Coil cleaner if heavy buildup
- Comb out bent fins
- LOTO during work
Indoor coil dirty:
- Often biological / dust buildup
- Cleaning more involved
- Sometimes pull from cabinet
- Cleaning chemicals available
Capacitor testing
Start capacitor (compressor):
- Common failure
- Bulged top = failed
- Test with multimeter (microfarads)
- Replace if outside ±10% of rated
Run capacitor (compressor):
- Allows compressor to run efficiently
- Failure: compressor draws more current
- Replace
Run capacitor (motor):
- For PSC motors
- Same approach
Contactor
Function: 24V signal from thermostat closes 240V to compressor + fan
Failure modes:
- Contacts welded closed (compressor runs constantly)
- Contacts pitted (intermittent operation)
- Coil failed (won't close)
Replacement: simple; verify same size + voltage.
TXV (Thermal Expansion Valve)
For systems with TXV (not piston / orifice):
TXV stuck open:
- Floods evaporator
- Low superheat
- Possible compressor damage
TXV stuck closed:
- Starves evaporator
- High superheat
- Reduced cooling
Diagnosis:
- Superheat measurement
- Sometimes replace if suspect
Compressor
Failed compressor (most expensive component):
- No cooling
- May hum
- High electrical draw
- Won't start
Diagnosis:
- Check capacitor first
- Check contactor
- Check incoming voltage
- Compressor windings test
- If failed: replace OR replace whole condenser
Drainage
Condensate drain clogged:
- Water in pan
- Float switch tripped (some systems)
- AC shuts off
- Sometimes water damage
Diagnosis:
- Inspect drain pan
- Check drain line for clog
- Clear with shop vac OR snake
- Flush + treat to prevent recurrence
Common shortcut traps
Adding refrigerant without finding leak:
- Solves problem temporarily
- Leak continues; problem returns
- EPA violation (knowingly adding to leaking system)
- Always find + repair leak
References
- ACCA Manual J + S + D
- EPA Section 608 (refrigerant)
- AHRI rating standards
- Manufacturer service manuals
- Manuall internal: Refrigerant Types Reference, Superheat + Subcool Charging