Ohm's Law + Power Formula for Trades Reference

Why this matters

Ohm's Law + power formula are the foundation of electrical work. Every multimeter reading, every breaker sizing, every motor diagnosis traces back to these relationships. The tech who's fluent in them diagnoses faster + sizes equipment correctly. This is the field card.

The four basic quantities

Voltage (V OR E): electrical pressure (volts)

  • Pushes current through circuit
  • Measured between two points
  • Single-phase residential: 120V OR 240V

Current (I): electrical flow rate (amperes / amps)

  • Quantity of electrons moving
  • Measured in series (clamp meter most common)
  • Determines wire size + breaker

Resistance (R): opposition to current (ohms / Ω)

  • All conductors have some
  • Heating elements + motor windings have specific resistance
  • Measured with circuit de-energized

Power (P): rate of energy use (watts / W)

  • Volts × amps for resistive loads
  • Determines equipment capacity + utility bill
  • Often kilowatts (kW = 1,000W)

Ohm's Law

E = I × R

Voltage equals current times resistance.

Rearranged:

  • I = E ÷ R (current = voltage divided by resistance)
  • R = E ÷ I (resistance = voltage divided by current)

Memorize one form; derive others.

Practical Ohm's Law examples

Heater element:

  • Element resistance: 12Ω
  • Supply voltage: 120V
  • Current: I = 120 ÷ 12 = 10A

Verify reading:

  • Element should draw 10A
  • Reading higher = shorted (less resistance)
  • Reading lower = open (more resistance)
  • Reading zero = open circuit

Motor winding:

  • Spec'd resistance: 8Ω
  • Measured: 8.2Ω
  • Within tolerance; winding OK

Spec'd: 8Ω; measured: 0.1Ω:

  • Short circuit between windings
  • Motor failure
  • Replace

Spec'd: 8Ω; measured: infinite:

  • Open winding
  • Motor failure
  • Replace

Power formula

P = E × I (for DC + resistive AC)

Power equals voltage times current.

For motors + reactive loads:

  • P = E × I × PF (power factor)
  • PF typically 0.7-0.95 for motors
  • Reactive power separate calculation
  • Most service calculation: E × I sufficient estimate

Rearranged:

  • I = P ÷ E (current = power divided by voltage)
  • E = P ÷ I (rarely used)

Practical power examples

Refrigerator:

  • Nameplate 700W running
  • Voltage: 120V
  • Current: I = 700 ÷ 120 = ~5.8A

Verify amp draw:

  • Clamp meter on cord
  • Should read ~5.8A running
  • Higher = motor straining (failing)

Water heater:

  • 4500W element
  • Voltage: 240V
  • Current: I = 4500 ÷ 240 = 18.75A

Breaker size:

  • 18.75A continuous load × 125% (NEC) = 23.4A
  • 30A breaker minimum
  • Code-compliant

AC condenser:

  • Nameplate 3500W
  • Voltage: 240V
  • Current: I = 3500 ÷ 240 = ~14.6A

Combining Ohm's Law + Power

P = E² ÷ R OR P = I² × R

Useful for:

  • Heater element wattage from resistance
  • Heat generated in wire (I²R losses)
  • Voltage drop calculations

Example: I²R losses:

  • 50A current through wire
  • 0.05Ω wire resistance (long run small gauge)
  • Power lost as heat: 50² × 0.05 = 125W
  • Significant; wire warms + voltage drops

Series circuit math

Resistors in series:

  • Total resistance = sum
  • R_total = R1 + R2 + R3

Current:

  • Same through all (series circuit)

Voltage:

  • Divides across each resistor proportionally

Example: Series christmas lights:

  • 50 bulbs, each 2.4V
  • Total = 120V
  • One out = all out (open circuit)

Parallel circuit math

Resistors in parallel:

  • Total resistance = 1 / (1/R1 + 1/R2 + 1/R3...)
  • Always LESS than smallest resistor

Voltage:

  • Same across all (parallel)

Current:

  • Divides through branches inverse to resistance
  • Lower resistance branch = more current

Example: Household circuit:

  • All outlets parallel
  • Each device sees 120V
  • Each draws different current

Practical parallel example

Bedroom circuit:

  • Lamp: 100W = 0.83A
  • Phone charger: 5W = 0.04A
  • TV: 80W = 0.67A
  • Heater: 1500W = 12.5A

Total current: 0.83 + 0.04 + 0.67 + 12.5 = ~14A

On 15A circuit: near max; one more device could trip. On 20A circuit: comfortable margin.

AC vs DC

Ohm's Law applies to both:

  • DC: straightforward
  • AC: same for resistive loads (heaters)
  • AC: more complex for motors / transformers (reactance)

For practical residential service:

  • Resistive: heaters, incandescent, electric stove elements
  • Inductive: motors, transformers, fluorescent ballasts
  • Capacitive: certain loads, capacitor banks

Reactance + impedance

For inductive loads (motors):

  • Inductive reactance (X_L) at AC frequency
  • Adds to resistance
  • Impedance (Z) = total opposition
  • Z = √(R² + X_L²)

Practical implication:

  • Motor draws more current than R alone suggests
  • Power factor < 1
  • Account in sizing

For typical residential: most service tech uses simple V × I × PF approximation.

Voltage drop

Common diagnostic + design concern:

Long wire run:

  • Wire has resistance per foot
  • Voltage drops along length
  • At end of run, less voltage than source

Calculation:

  • V_drop = I × R_wire
  • R_wire = ρ × L ÷ A (resistivity × length / cross-section)

Practical rule:

  • 3% maximum voltage drop typical
  • 5% maximum branch + feeder combined

Example:

  • 240V circuit, 50A load
  • 100 ft run, 8 AWG copper
  • 8 AWG: ~0.78Ω per 1000 ft
  • Round trip 200 ft: 0.156Ω
  • V_drop = 50 × 0.156 = 7.8V
  • 7.8 ÷ 240 = 3.25% (just over limit)
  • Consider larger wire

Wire ampacity

NEC tables:

  • 14 AWG copper: 15A (60°C column for branch)
  • 12 AWG: 20A
  • 10 AWG: 30A
  • 8 AWG: 40A (60°C); 50A (75°C)
  • 6 AWG: 55A (60°C); 65A (75°C)
  • 4 AWG: 70A (60°C); 85A (75°C)

Sizing logic:

  • Calculate load
  • Apply 125% for continuous
  • Match wire to current
  • Match breaker to wire

Heat dissipation

Power dissipated in wire = I² × R

  • Heats wire
  • Reduces ampacity if cluster
  • Sometimes derate per NEC

Loose / corroded connection:

  • Higher resistance
  • More heat
  • Eventually arc
  • Fire risk

Tight connections matter.

Calculating amp draw for diagnosis

Compare measured to expected:

For element:

  • Nameplate watts ÷ voltage = expected amps
  • Measure with clamp meter
  • Within ±10% = OK
  • Higher = short (replace)
  • Lower = open partial (replace)
  • Zero = open complete (replace)

For motor:

  • Nameplate FLA (Full Load Amps)
  • Measure under load
  • Higher than FLA = motor straining
  • Lower = light load (sometimes OK)

Three-phase calculations

For commercial three-phase:

  • P = E × I × 1.732 × PF
  • 1.732 = √3 (square root of 3)
  • Three-phase relationship

Example: 480V three-phase motor:

  • 10 HP motor
  • ~7,460W (746W per HP)
  • Current per leg: I = 7460 ÷ (480 × 1.732 × 0.85) ≈ 10.5A
  • Nameplate confirms

Power factor

For motors:

  • Real power (kW) - useful work
  • Apparent power (kVA) - what utility supplies
  • Power factor = kW ÷ kVA

Lower PF:

  • More current for same useful work
  • Inefficient
  • Commercial customers pay penalty

References

  • NEC (National Electrical Code) ampacity tables
  • IEEE electrical engineering references
  • Standard electrical theory textbooks