Switches + Receptacles Types Reference
Why this matters
Wrong device for application = code violation OR safety hazard. Customer with a 15A outlet on a 20A circuit, no GFCI in the bathroom, OR a single-pole switch where 3-way needed - gets it wrong, calls back, loses trust. The right device every time = solid work. This is the field card.
Switch types
Single-pole: one switch controls one light. Most common. Two screw terminals (one black, one brass). No on/off marking required.
Three-way: two switches control one light (top + bottom of stairs). 3 screws (1 common dark, 2 travelers brass). NO on/off marking.
Four-way: middle switch in 3-or-more-location control. Between two 3-way switches. 4 screws.
Double-pole: 240V circuit; 2 hot wires switched simultaneously. 4 screw terminals.
Dimmer: switches AND varies brightness. Incandescent + LED-compatible dimmers differ.
Motion sensor: PIR sensor + switch; lights on with motion.
Smart switch (Wi-Fi, Z-Wave, Zigbee): home automation; some need neutral, some don't.
Pilot light switch: indicator lamp shows when switched on (basement, exterior).
Timer switch: digital countdown OR programmable; bath fan + outdoor lights.
Receptacle types
15A standard duplex (NEMA 5-15R): most common residential outlet. 120V, 15A.
20A duplex (NEMA 5-20R): one slot perpendicular (T-shaped). Required on dedicated 20A circuit.
240V outlets:
- 30A dryer (NEMA 14-30R): four-prong
- 50A range (NEMA 14-50R): four-prong, used for ranges + EV chargers
- 30A older dryer (NEMA 10-30R): three-prong; no separate ground (legacy)
- 50A older range (NEMA 10-50R): three-prong; legacy
GFCI (Ground-Fault Circuit Interrupter): trips on imbalance to earth. Required: kitchen counter, bath, garage, outdoor, basement, laundry. NEC 210.8.
AFCI (Arc-Fault Circuit Interrupter): trips on series + parallel arc faults. Required: most habitable rooms. NEC 210.12.
Dual-function (CAFCI + GFCI): combination protection.
USB-integrated receptacle: built-in USB ports. Limited charging speed (typically 2.1A per port).
Tamper-resistant (TR): child-safety shutters; REQUIRED on all new residential receptacles per NEC 406.12.
Weather-resistant (WR): outdoor-rated for damp/wet locations.
In-use weatherproof cover: required outdoor with continuously-plugged cord.
Receptacle ratings
| NEMA | Volts | Amps | Use |
|---|---|---|---|
| 5-15 | 125V | 15A | Standard outlet |
| 5-20 | 125V | 20A | Kitchen counter, dedicated |
| 6-15 | 250V | 15A | Light 240V appliance |
| 6-20 | 250V | 20A | Window AC |
| 6-30 | 250V | 30A | Dryer (legacy) |
| 6-50 | 250V | 50A | Range (legacy), welder |
| 10-30 | 125/250V | 30A | Older dryer 3-prong |
| 10-50 | 125/250V | 50A | Older range 3-prong |
| 14-30 | 125/250V | 30A | Modern dryer 4-prong |
| 14-50 | 125/250V | 50A | Modern range, EV charger |
Switch wiring basics
Single-pole: line in (black) to one terminal, load out (black) to other. Neutral straight through (white passes; not switched). Ground to green screw.
3-way (with 14/3 cable): dark screw = common (line OR load); 2 brass screws = travelers. Red + black wires of 14/3 are travelers; white usually neutral except in switch-loop scenarios.
Switch loop (older wiring): only 14/2 (no neutral); requires re-marking. New code requires neutral at switch box.
GFCI installation
At outlet (typical kitchen): wired LINE in (incoming power) + LOAD out (downstream outlets). Downstream outlets all GFCI-protected.
At breaker: whole circuit GFCI-protected from panel.
Self-test feature (post-2015): GFCI tests itself every few seconds; lights status LED.
AFCI installation
At breaker (most common): AFCI breaker replaces standard.
Combination AFCI/GFCI breaker covers both.
Common AFCI nuisance trips: motor brushes (vacuum, hair dryer); cheap LED drivers; cordless tool chargers. Resolve by replacing the noisy device OR upgrade to a less-sensitive AFCI breaker.
Locations where GFCI required (residential)
- All kitchen counter outlets
- Bath outlets
- Garage outlets
- Outdoor outlets
- Pool / spa area
- Basement (unfinished + finished both)
- Crawl space
- Laundry
- Wet bar
- Boathouse / dock
- Within 6 ft of any sink
Locations where AFCI required (residential)
- Most habitable rooms (bedroom, living, dining, family, hallway)
- Recreation room, library, sunroom
- Closets, dens
Common device mistakes
15A on 20A circuit (single device limit OK; multiple receptacles must be 20A on 20A circuit per NEC 210.21). Missing tamper-resistant (TR) on new install. No GFCI in required location. AFCI omitted from required circuit. Pigtail neutral wire to old GFCI line side (wires backstabbed; failed). Wire-nut splice in shallow box (overfill). Decora device in narrow plate (won't fit). Smart switch without neutral wire (won't function).
Spec-grade vs commercial-grade
For pro service work: spec-grade minimum; commercial for high-use locations.
Color coding
White: standard interior, neutral.
Almond: matches older trim.
Ivory: matches older trim variant.
Black: commercial / industrial.
Gray: commercial / utility.
Dimmer compatibility
Incandescent: any dimmer works.
Halogen: dimmable.
LED: requires LED-rated dimmer; some bulbs don't dim smoothly.
CFL: most don't dim; some "dimmable" CFL work poorly.
Fluorescent tube: needs special dimmer + dimmable ballast.
Smart bulbs (Hue, LIFX): do NOT use dimmer; smart-bulb has own dimming.
Receptacle install workflow
- Confirm power off + verify dead with multimeter
- Remove old device + photo wiring
- Strip new wire (typical 1/2" - 5/8" exposed)
- Side-screw termination (don't backstab); torque 16 in-lb residential
- Pigtail multiple wires + use wire nut + 6" pigtail to device
- Push device into box without binding wire
- Mount + plate
- Power on + test (voltage tester at all 3 outlets if duplex)
Code compliance check
- TR on all residential receptacles (NEC 406.12)
- GFCI in required locations (NEC 210.8)
- AFCI on required circuits (NEC 210.12)
- 18-inch rule (kitchen-counter receptacle spacing)
- 6-foot rule (within 6 ft from any point on a wall)
The single most-useful device-install habit is the SIDE-SCREW + TORQUE every time, instead of backstab. Backstab connections (push-in spring on rear of device) fail over time - spring loses tension, connection arcs, outlet stops working OR shorts. Side-screw termination with proper torque (16 in-lb residential) holds for the life of the device. 30 seconds extra per device = callback work. Pro electricians don't backstab; the cheap connections are a feature for the DIYer, not the licensed tech.
References
- NEC Article 210 (Branch Circuits)
- NEC 406 (Receptacles + Cord Connectors)
- NEC 404 (Switches)
- UL 498 (Attachment Plugs + Receptacles)
- UL 943 (Ground-Fault Circuit Interrupters)
- Manuall internal: Wire Termination Types, Breaker + Panel Reference